Skip to main content
Fiber Teknik

Chemical Storage Tanks7 min read

Choosing a Chemical Storage Tank: Resin, Temperature and Double-Wall Decisions

Matching the resin to the chemical, temperature limits, double-wall tanks and secondary containment, nozzles and venting, and what to tell the manufacturer.

By Fiber Teknik Mühendislik Ekibi

Choosing a Chemical Storage Tank: Resin, Temperature and Double-Wall Decisions
On this page
  1. 1. Matching the resin to the chemical
  2. 2. Temperature limits
  3. 3. Double walls and secondary containment
  4. 4. Nozzles, venting and fittings
  5. 5. Installation and operation
  6. What to tell the manufacturer
  7. How Fiber Teknik helps

The short answer: a safe GRP chemical tank starts with three decisions. The resin is chosen for the type and concentration of the chemical; the temperature has to stay within the limits of that resin; and if the chemical is hazardous, you decide at the outset whether the tank should be double-walled. Nozzles, venting and instrumentation are designed together with these decisions, not bolted on afterwards.

Below we explain how each decision is made and what information the manufacturer needs from you.

1. Matching the resin to the chemical

In a GRP tank, the part that resists the chemical is the set of inner layers in contact with the liquid: the gelcoat reinforced with a C-glass veil, and the corrosion barrier behind it. The structural wall, the E-glass wound at ±55° and 90°, carries the load and should never see the chemical directly. So choosing a resin really means choosing the inner layers.

ResinResistanceTypical use
OrthophthalicLow–mediumAtmospheric exposure, simple water storage
IsophthalicMedium–highDrinking water, moderate chemical duty, underground tanks needing hydrolysis resistance
Vinyl esterVery highAcids, alkalis, solvents, oxidisers; high-temperature process tanks
Novolac vinyl ester / epoxyHighestHarsher temperature and chemical duty, specified per project

For concentrated acids such as hydrochloric (HCl), sulphuric (H₂SO₄) and nitric acid, and for alkalis such as sodium hydroxide (NaOH), vinyl ester is the standard starting point. As acid concentration and temperature rise, the corrosion barrier is built with pure vinyl ester or novolac vinyl ester to stop acid vapour from permeating the resin.

One important point: different concentrations of the same chemical can call for different resins. "Acid tank" is not a specification. Give the chemical name, its concentration, and any other components of the mixture.

2. Temperature limits

Our chemical tanks have a general operating range of -30°C to +110°C, but the upper end does not apply to every resin and every chemical. Depending on resin type, tanks go up to 90–110°C; with some acids the limit sits around 80–90°C. As a rule, chemical attack speeds up as temperature rises, so a chemical that an isophthalic resin handles at 20°C may need vinyl ester at 80°C.

Temperature situations to watch:

  • Exothermic reactions: the liquid heats up during dilution or neutralisation. Design for that peak, not for the normal storage temperature.
  • Heating and cooling: if a coil or jacket is fitted, laminate thickness and structural support are calculated for it.
  • Hot cleaning: if the tank is cleaned periodically with steam or hot water, state the highest cleaning temperature too.

3. Double walls and secondary containment

If you store a hazardous, toxic or flammable chemical, a single-wall tank needs secondary containment around it. There are two routes: place the tank inside a concrete bund, or build the tank double-walled.

A double-wall tank has a gap between the inner vessel and the outer shell. If the inner vessel leaks, the liquid is held in that gap instead of reaching the ground. Level or moisture sensors placed in the gap give early warning. These tanks are designed with the requirements of ATEX, Seveso III and national environmental regulations in mind; which regime your site falls under, and how secondary containment must be documented, is settled in your own permitting process.

SituationSingle wall + concrete bundDouble-wall tank
Limited floor spaceBund takes extra areaCompact solution
Leak detectionVisual inspectionSensor in the interstitial gap
Civil worksSeparate concrete work for the bundTank arrives ready from the factory
Bund already existsSensible optionAdded benefit may be limited

A practical rule: on a new site with limited space and a hazardous chemical, consider a double wall from day one. If a suitable bund already exists, a single-wall tank may be enough.

4. Nozzles, venting and fittings

Much of a chemical tank's safety is decided at the connections rather than in the shell. The roof should be designed to take a vent, a level gauge and a safety valve. On dosing tanks, the flange area is reinforced for the vibration and torque of the mixer motor, and ready-made connections are left for a level sensor, a pH/ORP probe and a temperature gauge.

Points to review:

  • Diameter, position and flange standard of the fill and draw-off nozzles.
  • The vent: the tank must breathe while filling and emptying, and acid vapour should be led to a controlled point, connected to a gas scrubber if needed.
  • Bottom shape: conical or sloped if you need full drainage.
  • Manway, ladder and platform requirements.
  • For process tanks, whether there is vacuum or light pressure (0.5–1 bar).

5. Installation and operation

Even a well-designed tank is stressed if it is installed badly. The points below are general engineering rules:

  • Flat, load-bearing base: a flat-bottomed tank must sit evenly across its whole base. Point loads or hollows put stress into the bottom.
  • Pipe loads: the weight and thermal expansion of connected pipework should not hang on the nozzles. Support pipes independently and use flexible connectors where needed.
  • Labelling and records: the stored chemical, its concentration and the maximum temperature should be clearly marked on the tank. Check with the manufacturer before switching to a different chemical.
  • Periodic inspection: discolouration, blistering or softening of the inner surface are the first signs that the corrosion barrier is under strain. Inspect the liner and fittings such as gaskets and bolts during planned shutdowns.

What to tell the manufacturer

Working through this list before you ask for a quote lets the right resin and wall build-up be specified the first time:

  1. Chemical name and concentration (%); for mixtures, every component.
  2. Normal operating temperature and the maximum (exothermic peak, cleaning).
  3. Density of the liquid.
  4. Net capacity and any limit on diameter or height.
  5. Vertical, horizontal or rectangular form; flat or conical bottom.
  6. Indoors or outdoors; exposure to UV and wind.
  7. Double wall required, or details of an existing bund.
  8. Nozzle list: size, position, flange type; mixer, coil and sensor requirements.
  9. The design standard you want followed (EN 13121-3, BS 4994 or ASTM D3299).

How Fiber Teknik helps

Fiber Teknik builds chemical storage and process tanks from 1,000 to 250,000 litres in vinyl ester, novolac epoxy, bisphenol-A and isophthalic resin systems, referencing EN 13121-3, BS 4994 and ASTM D3299. You will find the options on our chemical tanks page and the details of resins and wall build-up on our technology page. When you have the information above ready, send it to our engineers with the quote button on this page.

Share
Back to Blog
Chemical Storage Tanks

Engineering consultation · reply within 24h

Engineering support for your storage project

Share your stored medium and target volume; our engineers calculate resin compatibility and wall thickness within 24 hours.

Get Free Quote

Get a Free Quote for Your Project

We're ready to listen to your needs and offer custom solutions. Our expert engineers will contact you as soon as possible.

WhatsApp
+90 (533) 594 68 50